Technical data

Configuration
CPU 317T: Technology Functions
A5E00251798-03
4-55
Parameter Value Description
Disabled Distance up to BERO detection not monitored
Max. distance to BERO
Enabled
Monitoring of the distance between the start
of the homing function and BERO detection. If
the difference in this distance exceeds the
configured distance, the corresponding
technology DB indicates error 801D. The
homing function is canceled.
Disabled Distance to go to the zero mark is not
monitored
Max. distance to zero mark
Enabled Monitors the distance an axis travels between
the BERO and the zero mark. If the
difference in this distance exceeds the
configured distance, the corresponding
technology DB indicates error
801D. The
homing function is canceled.
Passive homing in "BERO only" mode
Axis homing starts with the detection of the configured edge of the BERO signal.
The axis is set to the position value at the Position input of the technology function
"MC_Home."