7 COMMISSIONING & CUSTOMER HAND OVER
7.1 Commissioning
When all connections have been completed the solar water heater can be filled with
water.
1. Before turning on the cold water supply to the system, open one hot tap within the
household to release air from the system during the filling process. Do not leave
the open tap unattended during the filling process.
2. Turn on the cold water supply and wait for the system to fill.
3. When water flows from the open hot tap without air bursts then the hot tap can be
closed. This will now pressurise the solar water heater system.
4. Once the system is pressurised, all connections on the water heater must be
checked for leaks and repaired if necessary.
5. When the system is proven water tight, power and/or gas can be applied to the
AES system.
6. To test that the element is operational turn the circuit breaker in the switch board
on and off, you should see the power meters speed change during this action.
7. For gas AES systems, turn on a hot water tap and the gas heater will ignite
provided the water temperature is less than 60 °C.
7.2 Filling & Commissioning the Closed Circuit Jacket
When filling the jacket with glycol it is essential that the main tank is filled with water and
pressurised prior to filling the closed circuit. Refer to section 7.1 above.
Do not fill the closed circuit system with any toxic solution. Only use the solar transfer
fluid as specified by your TS system distributor. There is a real risk to public health if the
wrong solar glycol solution is used.
The solar transfer fluid is of food grade and non-toxic. However, care must be taken
when handling not to spill or accidentally consume. Always use the solar transfer fluid as
specified and outlined in section 7.2.1 below.
7.2.1 Approved Solar Transfer Fluids
Name: ST-5 Solar Transfer Fluid
Description: Propylene Glycol
Appearance: Red liquid.
To ensure adequate frost protection, use the following quantity of ST-5 to maintain glycol
above 40% of solution:
1. TS 180/C system: 1 bottle 4.5 litres total
2. TS 300/C system: 2 bottles 9 litres total
7.2.2 Required Equipment
1. 25 litre container x1
2. 4 metre length of ½” (15mm) x1
3. Pressure Test Block x1
4. Bicycle Pump x1
5. Funnel with ½” (15mm) connection x1
6. Square key.
7. ST-5 solar transfer fluid supplied with the system.