Item No. Part No. Description Qty
1 60-1003 Union, RP3/4” - C22mm, Sub Assy 2
2 60-1004 Plug, Compression, 22mm, Sub Assy 1
3 60-1009 Valve, Caleffi, 100kPa 1
4 60-1056 Valve, P&T, 850kPa 1
5 60-1083 Union, Collector Elbow, Thermosiphon, SAssy 2
6 60-1119 Union, Fill Fitting, 22mm, SAssy 1
7 60-1131 Cold Pipe, 182/BC/C/XX, SAssy 1
8 60-1132 Hot Pipe, 182/BC/C/XX, SAssy 1
9 60-3030 Rail, Collector, Steel Angle, 1 Panel 1
10 60-4000 Strap, Mounting, Tank, Type A 2
11 60-4004 Clamp, Mounting, Tank, Type A 2
12 60-4011 Strap, Collector, Type C 2
13 75-4000 Nut, Hex, SS, M8 x 1.25 2
14 75-4001 Washer, Plain, Stainless Steel, M8 2
15 75-4002 Set Screw, Hex, SS, M8 x 1.25 x 20 2
16 75-4016 Screw, Self Drilling, Pan, SS, CR, #8 x 13mm 6
17 E20 Solar Collector, E20BC, E20SB 1
18 S180/C/KE Tank Assembly, TS180/C/V 1
4.9 Plumbing connections - Open Circuit Models
Cold water connection
A check valve and a stop cock must be fitted to the cold water supply pipe work.
1.
2.
Cold water expansion relief valve
Fit the 700 kPa pressure relief valve supplied in the Parts Box in the cold water supply pipe after
the check valve, stop cock and (if required) pressure limiting valve assembly.
Hot water connection
Use the ¾BSP x 22mm fitting supplied in the parts kit to connect the hot water supply to the
storage tank outlet connection (Detail A) adjacent the P&T valve and marked with a blue disc.
4.9.1
4.9.2
4.9.3
Connect the cold water supply to the end of the ¾BSP female thread of the Tee piece in the
cold down pipe assembly (Detail A).
It is mandatory that a check valve and stop cock are fitted to the cold water supply pipe work.
Where the water supply pressure is greater than 550 kPa, a 500 kPa pressure limiting valve
must be fitted to limit the supply pressure.
4 Installation Instructions