System information
1. CONFIGURATION OVER WEB BROWSER
Continued from previous page
OID Description
.1.3.6.1.4.1.30140.2.1.6.0 Binary input BIN2 (values 0,1)
.1.3.6.1.4.1.30140.2.1.7.0 Binary input BIN3 (values 0,1)
.1.3.6.1.4.1.30140.2.1.8.0 Binary input BIN4 (values 0,1)
.1.3.6.1.4.1.30140.2.1.9.0 Binary output OUT1 (values 0,1)
Table 55: Object identifier for CNT port
For the expansion port M-BUS the following range of OID is used:
OID Description
.1.3.6.1.4.1.30140.2.2.<address>.1.0 IdNumber – meter number
.1.3.6.1.4.1.30140.2.2.<address>.2.0 Manufacturer
.1.3.6.1.4.1.30140.2.2.<address>.3.0 Version – specified meter version
.1.3.6.1.4.1.30140.2.2.<address>.4.0 Medium – type of metered medium
.1.3.6.1.4.1.30140.2.2.<address>.5.0 Status – errors report
.1.3.6.1.4.1.30140.2.2.<address>.6.0 0. VIF – value information field
.1.3.6.1.4.1.30140.2.2.<address>.7.0 0. measured value
.1.3.6.1.4.1.30140.2.2.<address>.8.0 1. VIF – value information field
.1.3.6.1.4.1.30140.2.2.<address>.9.0 1. measured value
.1.3.6.1.4.1.30140.2.2.<address>.10.0 2. VIF – value information field
.1.3.6.1.4.1.30140.2.2.<address>.11.0 2. measured value
.1.3.6.1.4.1.30140.2.2.<address>.12.0 3. VIF – value information field
.1.3.6.1.4.1.30140.2.2.<address>.13.0 3. measured value
.
.
.
.
.
.
.1.3.6.1.4.1.30140.2.2.<address>.100.0 47. VIF – value information field
.1.3.6.1.4.1.30140.2.2.<address>.101.0 47. measured value
Table 56: Object identifier for M-BUS port
The meter address can be from range 0..254 when 254 is broadcast.
Since firmware 3.0.4 all v2 routers with board RB-v2-6 and newer provide information
about internal temperature of device (OID 1.3.6.1.4.1.30140.3.3) and power voltage (OID
1.3.6.1.4.1.30140.3.4).
67