User Manual

3
.
OUT 2 COM OUT 2 COM TB3-6
5. LOGIC OUTPUT:
The logic output is available on the 1/0 terminal block TB2 on the CPU assembly.
Trip 1: TB2-2
Trip 2: TB2-3
The 1/0 must be selected by jumper plugs P4 and P5 for OUT on the CPU assembly.
P4 set for OUT at S4
P5 set for OUT at S5
A trip “ON” condition “relay energized” is a logic “0”
6. TRIP POINT SETUP
SELECTING TRIP PT SETUP:
1. MAIN SETUP: Close rocker switch 1 only.
Press the
“NO” key until the "SETUP 1/0 ?" is selected and then press
“YES” key.
In the SETUP 1/0 press the
”NO” key until the "SETUP TRIP PT ?" is
selected and then press
“YES” key.
2. SET-UP 1/0 (direct): Close rocker switch 3 only.
Indicator is placed directly into the 1/0 set up mode.
In the SETUP 1/0 press the
“NO” key until the "SETUP TRIP PT ?" is
selected and then press
“YES” key.
Numeric Data Entry
Each press of the right or left key moves the position of the digit to be
changed. This position is marked by the flashing of the selected digit.
The selected digit is then incremented or decremented using the up / down
I/O 2
IN
S4
I/O 1
RETURN
OUT
S5
Jumper plugs shown on S4
and S5 are configured as
OUTPUTS.
TB2
(
di
g
ital common
)