Owner's manual
Auto Selection Default Tables 63
9.0 Auto Selection Default Tables
Auto Selection (Gage) Default Table
Parameter 3 PSIG 10 PSIG 15 PSIG 25 PSIG 50 PSIG 100 PSIG 250 PSIG 500 PSIG
CAPACITY 3 10 15 25 50 100 250 500
CT-BY 0.0005 0.001 0.002 0.002 0.005 0.01 0.02 0.05
UNITS (Cal) PSI PSI PSI PSI PSI PSI PSI PSI
TYPE GAGE GAGE GAGE GAGE GAGE GAGE GAGE GAGE
CAL SPAN 1 0.3 1 1.5 2.5 5 10 25 50
CAL SPAN 2 0.6 2 3.0 5.0 10 20 50 100
CAL SPAN 3 0.9 3 4.5 7.5 15 30 75 150
CAL SPAN 4 1.2 4 6.0 10.0 20 40 100 200
CAL SPAN 5 1.5 5 7.5 12.5 25 50 125 250
CAL SPAN 6 1.8 6 9.0 15.0 30 60 150 300
CAL SPAN 7 2.1 7 10.5 17.5 35 70 175 350
CAL SPAN 8 2.4 8 12 20.5 40 80 200 400
CAL SPAN 9 2.7 9 13.5 22.5 45 90 225 450
CAL SPAN 10 3.0 10 15 25.0 50 100 250 500
HYSTERESIS 1.5 5 7.5 12.5 25 50 125 250
FILTR 55555555
DSP/SEC 33333333
ZERO % 22222222
ZERO+/-% 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
AZM +/- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
MOTION 11111111
MIN PRES OFF OFF OFF OFF OFF OFF OFF OFF
MAX PRES OFF OFF OFF OFF OFF OFF OFF OFF
PSI ON ON ON ON ON ON ON ON
KPa ON ON ON ON ON ON ON ON
mmHg0
•
C
ON ON ON ON ON ON ON ON
BAR OFF OFF OFF OFF OFF ON ON ON
inHg0
•
C
ON ON ON ON ON ON ON ON
mBAR ON ON ON ON ON ON ON ON
cmH
2
0
ON ON ON ON ON ON ON ON
kg/cm
2
OFF OFF OFF OFF OFF ON ON ON
inH
2
060
•
F
ON ON ON ON ON ON ON ON
inH
2
04
•
C
ON ON ON ON ON ON ON ON
ftseaH
2
0
ON ON ON ON ON ON ON ON
TORR ON ON ON ON ON ON ON ON
metrsH
2
0
ON ON ON ON ON ON ON ON
PASCAL ON ON ON ON ON OFF OFF OFF
mmH
2
04
º
C
ON ON ON ON ON ON ON ON
Table 9-1. Auto Selection (Gage) Default Table (3 PSIG – 500 PSIG)