Operation Manual
42 Operating the control software
BACnet Parameters Tab
– BACnet: with this setting you can activate ("MSTP" or "BACnet/IP") or
deactivate ("Off") the communication via the integrated BACnet interface.
Note: in order to activate the setting of this parameter the Condair RS
must be switched off and on again.
Important! The switching from "BACnet IP" to "BACnet MS/TP" is only
taken over after the restart, if the "Source" setting in the "Control Set-
tings" submenu is set to "Analog" or the corresponding BACnet mode!
The Integrated Controller does not switch, if for example "BACnet IP" is
selected, but the "Source" setting in the "Control Settings" submenu is
set to "BACnet MS/TP".
Factory setting: Off
Options: Off (BACnet interface deactivated)
MSTP (BACnet MSTP via RS 485 interface, Note:
the Condair RS is a slave-only BACnet MSTP
device)
BACnet/IP (BACnet/IP via RJ45 interface)
The following settings appear only, if the parameter "BACnet" is set to
"BACnet/IP".
– Device Name: with this setting you determine the name of the Condair
RS for the communication via the integrated BACnet interface.
– Device Description: with this setting you determine a short descrip-
tion of the Condair RS.
– Device Location: with this setting you determine the designation of
the unit location.
– Node ID: with this setting you assign a node ID to the Condair RS for
the communication via the BACnet/IP protocol.
Factory setting: 1001
Setting range: 1-9999999
– BACnet IP Port: with this setting you assign a IP port number for the
Condair RS.
Factory setting: 47808
Setting range: –––
– BACnet MSTP MAC: with this setting you assign a MSTP MAC ad-
dress for the Condair RS.
Note: this setting does not have any effect for BACnet IP communication.
Factory setting: 128
Setting range: 128-254