40 Operating the control software
Network Parameters Tab
The following network settings are used only for the communication via the
integrated BACnet IP interface.
IP Type: with this setting you determine whether you want to assign the IP
Address, the Subnet Mask, the Standard Gateway as well as the Primary
and Secondary DNS address as xed values or whether these should be
dynamically assigned via a DHCP server.
Note: after 5 unsuccessful attempts at obtaining an address with DHCP
the system will revert to xed assignment
Factory setting: DHCP
Options: DHCP (dynamic assignment)
Fixed (xed assignment)
IP Address: with this setting you manually enter the IP Address of the
Condair RS.
Note: This IP Address is used if "IP Type" is set (or reverts) to "Fixed".
Subnet Mask: with this setting you determine the Subnet Mask of the IP
network.
Note: This Subnet Mask is used if "IP Type" is set (or reverts) to "Fixed".
Default Gateway: with this setting you determine the IP Address of the
Default Gateway.
Note: This IP Address for the Default Gateway is used if "IP Type" is set
(or reverts) to "Fixed".
Primary DNS: with this setting you determine the IP Address of the Primary
Domain Name Server (DNS).
Note: This IP Address for the Primary Domain Name Server is used if "IP
Type" is set (or reverts) to "Fixed".
Secondary DNS: with this setting you determine the IP Address of the
Secondary Domain Name Server (DNS).
Note: This IP Address for the Secondary Domain Name Server is used if
"IP Type" is set (or reverts) to "Fixed".
MAC Address: factory set MAC Address (Media Access Control) of the
Condair RS. Not modiable.
Host Name: Host Name of the Condair RS automatically generated by
the control. Format: "IC_"+"Serial number of the device". Not modiable.
BMS Timeout Tab
BMS Timeout: with this setting you determine the maximum time the
humidier will wait with no communication from the BMS network before
a BMS timeout warning is generated. Exceeding the timeout also stops
humidier operation if the signal source of the humidier is set to a BMS
input.
Factory setting: 300 s
Setting range: 1 ... 300 s