Operation Manual
35Operating the control software
– Operation with timer controlled capacity limitation
Activate the timer function (Setpoint Timers: "On"). If the setpoint
timer is activated, up to eight switching points (Event 1... Event 8) with
different humidity setpoints can be dened. Each switching point is
dened by a weekday or weekday range, the switching time and the
humidity setpoint in %rh.
Conguration notes:
– the settings of an event remain active up to the next event.
– the software does not c heck the plausibility of the timer settings.
Therefore, make sure your settings make sense.
– the On/Off timer overrides the humidity setpoint timer.
– Band Channel 1: with this setting you set the proportional range for the
internal P/PI controller in %rh.
Note: this setting appears only if the "Control Mode" is set to "RH P" or
"RH PI".
Factory setting: 15 %
Setting range: 6 ... 65 %
– ITime Channel 1: with this setting you set the integral time for the internal
P/PI controller.
Note: this setting appears only if the "Control Mode" is set to "RH PI".
Factory setting: 5 minutes
Setting range: 1 ... 60 minutes
– Setpoint Channel 2: with this setting you set the humidity setpoint for the
internal P/PI supply air controller in %rh.
Note
: this setting appears only if the "Control Mode" is set to "RH P" or
"RH PI" and "Control Channels" is set to "Dual".
Factory setting: 80 % (rh)
Setting range: 0 ... 95 % (rh)