Op. Cycle limit: with this setting you determine whether the On/Off switch-
ing delay is set to optimise the lifetime of the heating contactors ("On") or
whether the On/Off switching delay is reduced to optimise the precision
of control ("Off" – reduced life of heating contactors).
Note: This menu item appears only on units with normal control accuracy.
Factory setting: On
Options: On or Off
Consider Flicker Rule: with this setting you determine whether the
blocking time of the switching elements (Triac or contactor) are controlled
normally ("On") to maintain "Flicker"-regulations or whether the blocking
time is reduced to optimise the precision of the control ("Off").
Note: This menu item appears only on option P units with increased control
accuracy. On units with normal control accuracy the "Flicker"-regulations
are considered as standard.
Factory setting: On
Options: On or Off
Drain Mode Tab
Note: the "Drain Mode" tap with the corresponding settings appears only, if the drain cooling option and/
or the optional drain valve is installed and activated in the factory level.
Drain Cool: with this setting you can activate ("On") or deactivate ("Off")
the drain cooling option.
Note: if the drain cooling option is activated, the drain water is cooled
down below 60 °C.
Factory setting: Off
Options: Off or On
Complete Drain: with this setting you can activate ("On") or deactivate
("Off") the optional drain valve for the automatic draining of the scale col-
lector tank in standby operation.
Note: if the optional drain valve is activated, the Condair RS is completely
drained in standby operation (including scale collector tank) and relled
only after a humidity demand is present again.
Factory setting: Off
Options: Off or On