Operation Manual
26 Operating the control software
The following settings appear only, if "Water Mode" is set to "Calculated".
Important: the water quality and the water hardness of the supply water
must be known. Using wrong values for these two parameters may lead to
increased maintenance work and operating malfunctions.
– Water Quality: with this setting you determine the water quality of the
supply water.
Factory setting: Untreat. tap water
Options: Untreat. tap water (untreated water from tap water
network)
RO water low (RO water with low conductivity
<5 µS/cm)
RO water high (RO water with high conductivity
>5 µS/cm)
– Water Hardness: with this setting you determine the water hardness of
the supply water in °dH (german hardness degree).
Factory setting: 20.0 °dH
Setting range: 1.0 ... 30.0 °dH
– Maintenance Extended: with this setting you determine the interval
time in hours for the extended maintenance.
Factory setting: dependent on the steam capacity
Setting range: 100 ... 6'000 h
Standard settings dependent on the water quality
Steam
capacity
Water reduction time Maintenance interval time
Small Maintenance Extended Maintenance
Tap water * RO water ** DI water *** Tap water * RO water **
DI water ***
Tap water * RO water **
DI water ***
5 kg/h 30 min 180 min 360 min 500 h 3000 h 1500 h 3000 h
8 kg/h 20 min 180 min 360 min 500 h 3000 h 1500 h 3000 h
10 kg/h 20 min 180 min 360 min 500 h 3000 h 1500 h 3000 h
16 kg/h 10 min 180 min 360 min 450 h 3000 h 1350 h 3000 h
20 kg/h 7 min 180 min 360 min 400 h 3000 h 1200 h 3000 h
24 kg/h 7 min 180 min 360 min 400 h 3000 h 1200 h 3000 h
30 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
40 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
50 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
60 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
80 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
100 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
120 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
140 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
160 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
* The default settings for untreated tap water refer to a water hardness of 20 °dH or 36 °fH or 360 ppm, respectively
** Default settings for water from a reverse osmosis system (RO water) >5 ... ≤ 30 μS/cm
*** Default settings for de-ionized water (DI water) ≤ 5 μS/cm