Operation Manual

26 Operating the control software
The following settings appear only, if "Water Mode" is set to "Calculated".
Important: the water quality and the water hardness of the supply water
must be known. Using wrong values for these two parameters may lead to
increased maintenance work and operating malfunctions.
Water Quality: with this setting you determine the water quality of the
supply water.
Factory setting: Untreat. tap water
Options: Untreat. tap water (untreated water from tap water
network)
RO water low (RO water with low conductivity
<5 µS/cm)
RO water high (RO water with high conductivity
>5 µS/cm)
Water Hardness: with this setting you determine the water hardness of
the supply water in °dH (german hardness degree).
Factory setting: 20.0 °dH
Setting range: 1.0 ... 30.0 °dH
Maintenance Extended: with this setting you determine the interval
time in hours for the extended maintenance.
Factory setting: dependent on the steam capacity
Setting range: 100 ... 6'000 h
Standard settings dependent on the water quality
Steam
capacity
Water reduction time Maintenance interval time
Small Maintenance Extended Maintenance
Tap water * RO water ** DI water *** Tap water * RO water **
DI water ***
Tap water * RO water **
DI water ***
5 kg/h 30 min 180 min 360 min 500 h 3000 h 1500 h 3000 h
8 kg/h 20 min 180 min 360 min 500 h 3000 h 1500 h 3000 h
10 kg/h 20 min 180 min 360 min 500 h 3000 h 1500 h 3000 h
16 kg/h 10 min 180 min 360 min 450 h 3000 h 1350 h 3000 h
20 kg/h 7 min 180 min 360 min 400 h 3000 h 1200 h 3000 h
24 kg/h 7 min 180 min 360 min 400 h 3000 h 1200 h 3000 h
30 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
40 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
50 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
60 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
80 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
100 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
120 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
140 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
160 kg/h 5 min 180 min 360 min 350 h 3000 h 1050 h 3000 h
* The default settings for untreated tap water refer to a water hardness of 20 °dH or 36 °fH or 360 ppm, respectively
** Default settings for water from a reverse osmosis system (RO water) >5 ... ≤ 30 μS/cm
*** Default settings for de-ionized water (DI water) ≤ 5 μS/cm