Operation Manual
25Operating the control software
5.4 Conguration
5.4.1 Accessingthe"Conguration"submenu
5.4.2 Activating/deactivatingandcongurationofoptions–"Features"submenu
In the "Features" submenu you can determine different operating parameters of the Condair RS.
Water Management Tab
– Water Mode: with this setting you determine whether the ushing interval
time and the maintenance interval time for the small and the extended
maintenance are calculated automatically on the basis of parameters
water quality and water hardness (Setting: "Calculated") or whether the
ushing interval time and the maintenance interval time for the small and
the extended maintenance can be set manually (Setting: "Manual").
Factory setting: Manual
Options: Manual or Calculated
– Water Reduction: with this setting you can activate ("On") or deactivate
("Off") the automatic water reduction function.
CAUTION: Deativating the water reduction function when using drink-
ing water can lead to heavy scaling of the steam cylinder!
Factory setting: On
Options: On or Off
The following settings appear only, if "Water Mode" is set to "Manual".
Note: The settings for the parameters to be selected depend on the supply
water quality and the steam capacity of the unit and must be set in ac-
cordance with the following table. It may have to be adapted to the actual
circumstances during operation.
– Water Reduction Time: with this setting you determine the interval
time in minutes for the automatic ushing cycle.
Factory setting: dependent on the steam capacity
Setting range: 5 ... 720 minutes
– Maintenance Small: with this setting you determine the interval time
in hours for the small maintenance.
Factory setting: dependent on the steam capacity
Setting range: 100 ... 3'000 h
Password: 8808