User manual

35
Diagram 3-1-2-4
1. The top area displays the manufacturer and model name of ATS. Sometimes, the manufacturer
may not be shown. For example, “ATS” means that the model name is ATS. The bottom area
displays the serial number and firmware version of ATS.
2. The middle area displays the ATS Status Figure. There are five lights: S1, S2, SW1, SW2, F1
and three information frames. Also, there are some current lines in black or green.
3. The S1 is black when Input source 1 failed (no power on source). It will flash when the voltage or
frequency of source 1 is out of range or source 1 is unstable. It is green when source1 is OK.
The S2 for source 2 is the same. The SW1 is green when the load is powered by input source 1.
Otherwise, it is black. The SW2 is the same. The F1 in red indicates that the faults are detected,
such as overload fault, stick fault or over current. Otherwise, the F1 is green.
4. The information frame on the left of S1 displays the input voltage and frequency of Source 1. S2
is the same. If it is the preferred source, then the “Preferred Source” string is shown. Also, the
background color of the frame indicates whether it is the preferred source. If the background
color of frame is green, then it is the preferred source, otherwise, it is white. The frame on the
right of F1 displays the output information, such as output voltage, output frequency, output
current and load percentage.
5. The lines between S1 and SW1, between S2 and SW2, between SW1 and F1, between SW2
and F1 indicate the current. If there is current between them, the line is green. Otherwise, the
line is black.
If you select inverter from the List, details about all module of inverter system will be displayed on
the right side, Refer to the following diagram 3-1-2-5:
Diagram 3-1-2-5
2. Menu and Dialog
1) Auto Search Device
When user select "Auto Search Device" item from "System" Menu, Winpower will start searching
for the device connect to the computer’s serial port or USB port (for telecom power, the USB driver
must be installed; For ATS, A crossover RS232 cable will be needed that crosses pins 2 and 3, so
that pin 2 on one side is connected to pin 3 on the other.). See the following diagram 3-2-1-1 and
diagram 3-2-1-2. Winpower can monitor not more than four COM ports and one USB port in one
computer. Only on Windows 98/2000/2003/XP/Vista, Mac OS X and Linux (with kernel 2.6) can use
the USB port. For UPS, no USB driver is needed. But telecom power's USB communication only
works with Windows 2000/XP/Vista and need install the USB driver at directory USB driver.