User guide

Corporate Office: 724.584.5500 Instant Access 24/7 (Parts and Service): 800.458.1960 Parts and Service: 814.437.6861
48
Note:Occasionalbubblinginasightglassmayoccuratatimewhenloadconditionsarechangingandthe
expansionvalveisadjustingtothenewconditions.Thismomentaryoccurrenceisaresultofnormalchiller
operation.

Anotheruseforthesightglassischeckifthereismoistureintherefrigerationcircuit.
YStrainer
AYStrainerwitha20meshscreenisintheenteringchilledwaterlinetohelpprotectthe
evaporatorpassagesfromclogging.
AutomaticWaterMakeUp(Optional)
Withthisoption,awatersupplycanbeconnectedtothechillersothatthewaterlevelinthe
reservoirisautomaticallymaintained.Whenthewaterlevelinthereservoirdropsbelowthe
lowlevelonthefloatswitch,asolenoidvalvewillbeopenedtoallowfreshwaterintothe
system.Whenthewaterlevelreachesthehighlevelonthefloatswitch,thesolenoidvalveis
closed.
Note:Thisoptionisnotnormallyrecommendedforsystemsthatdependonaglycolsolutiontopreventfreeze
ups.Automaticwatermakeupmaycausereductionoftheglycolconcentration,whichmayresultinan
evaporatorfreezeup.
CoolantPump
Theclosecoupledcentrifugalpumpisequippedwithamechanicalsealandisconstructedof
stainlesssteel.Thepumpisfactorytestedforthespecifiedoperatingconditions.Thepump
motormeetsNEMAspecificationsandindustrystandards.
UpgradedPumps(Optional)
Thestandardpumpsthathavebeenselectedforeachsizechillerwillmeettherequirementsof
mostapplications;however,incertaininstances,largerpumpsmayberequiredtoprovidethe
desiredflowandpressureforaspecificapplication.Thehorsepowerofthepumpwillbe
indicatedonthechillernameplate.
PressureGauge
Apressuregaugeismountedonthebackpanelofthechiller.Thisgaugedisplaysthepressure
ofthecoolantatthedischargeofthepump.Itcanbeusedtodeterminetheapproximatepoint
onthepumpcurveinwhichthepumpisoperating.
Reservoir
Thereservoirismountedinsidethecabinet.Thereservoirismadeofpolyethyleneandisfully
insulated.Alevelsighttubeisincludedsothecoolantlevelcanbeobserved.Thereisa
removablecoveronthetopofthereservoir.Duringchilleroperationthereservoirshouldbeat
leasthalffull.Formostinstallationsthereservoirhassufficientcapacitytohandlecoolant
drainbackfromtheprocessequipmentwhichoccursduringchillershutdown.Forinstallations
withoverheadpipingrunsofover90feet,(27M)specialprecautionswillhavetobemade
duringinstallation(seeFigure3,onpage
9).