SetupScreens(Passwordis“000”)
Compressor Setup
Adjustthecutinandcutoutpointsforthe
refrigerationcompressor(s).CutinandCutOut
valuesarerelativetoSetpoint.
Temperature Alarm Settings
Adjustthetemperaturealarmpoints.“Hi”and
“Lo”designateWarningpoints.Thesystemwill
showanamberflashifoneofthesepointsis
reached,buttheunitwillnotshutdown.“HiHi
andLoLo”areCriticalAlarmPoints.Thechiller
willshutdownifoneofthesepointsisreached.
The“HiTempBypassTimer”isanadjustable
timerthatwillbypassthetemperaturewarnings
forsometimeafterstart‐up.
Freezestat Setup
SettheFreezestattothechilled water
temperatureshownforyourglycolsolution
concentrationperTable 3(onpage21).The
chillerwillhaveacriticalFreezestatalarmifthe
FreezestatsensordetectswateratthisSetpoin t.
Thesystemmaynotberestarteduntilthewater
reachestheSetpoint+the
Cut‐invalue.
Hot Gas Bypass PID
Ifthechillerseemstofunctionnormallybuthas
difficultymaintainingsetpoint,consultConair
CustomerServiceforassistancewithPIDTuning.