a. ThisisthecontrolsignalbeingsenttotheHotGasBypassValve.Percentage
correspondstopercentopen.Thereissomelaginvalveresponse,soitwillnot
correspondtotheexactvalvelocationatalltimes.
b. Thisisaheatingfunctionanditwillopento
preventtheSupplyTemperature
fromdroppingbelowtheSetpoint.
c. Itisnormalforthevalvetobeopenatsomepercentageatalmostalltimes.This
chillerisdesignedwithexcesscoolingcapacity,andthisvalvebalancesthat
excesscapacity.
d. AhissingnoiseemittedfromtheHotGasBypass
Valveistypicalwhenthevalve
isopen.
e. IftheSupplyWaterisconstantlyafewdegreesundersetpoint,theprocessison,
andtheHGBP%ishigh,theremaybeanelectricalormechanicalproblemwith
theHotGasBypassValve.Onemaynoticealackofahissingsoundinthiscase.
ActiveAlarmsScreen/AlarmHistory