33
Table 6 – ModBus Option Parameters (Integer Values)
Reg Description Read/Write Notes
4000 CONTROLLERBOARDTYPE R 0x5432=F20,0x5434=F40
4001 SOFTWAREVERSION R 100xversion,e.g.119=ver1.19
4002 MACHINESTATE R
0=Off,1=Stop,2=Run,3=RunFault2,4=RunFault3,
5=Fault1,6=FactoryMenu,7=UserMenu,
8=GetUserPassword,9=MasterReset
4003 INPUTTYPE0 R 0 = RTD2,1 = RTD3,2 = RTDPWC,4=0‐1V,5=TC
4004 INPUTTYPE1 R 0 = RTD2,1 = RTD3,2 = RTDPWC,4=0‐1V,5=TC
4005 INPUTTYPE2 R 0 = RTD2,1 = RTD3,2 = RTDPWC,4=0‐1V,5=TC
4006 INPUTTYPE3 R 0 = RTD2,1 = RTD3,2 = RTDPWC,4=0‐1V,5=TC
4007 DERIVATIVE R/W
4008 INTEGRAL R/W
4009 HEATCYCLERATE R
4010 COOLCYCLERATE R
4011 LOWALARMDELAY R
4012 HIALARMDELAY R
4013 DISPLAYUNITS R 0=DegF,1=DegC
4014 CONTROLLERTYPE R 0=TCU,1=Chiller
4015 BROWNOUTENABLED R 0=DISABLED,1=ENABLED
4016 AUTOTUNEENABLED R 0=DISABLED,1=ENABLED
4017 SEALSAVERENABLED R 0=DISABLED,1=ENABLED
4018 REMHEATCOOLENABLED R 0=DISABLED,1=ENABLED
4019 PURGEENABLED R 0=DISABLED,1=ENABLED
4020 CRASHCOOLENABLED R 0 =DISABLED, 1=ENABLED
4021 FLOWENABLED R 0=DISABLED,1=ENABLED
4022 NOTUSED X
4023 NOTUSED X
4024 REMSETPOINTENABLED R 0=DISABLED,1=ENABLED
4025 AUTOSTARTENABLED R 0=DISABLED,1=ENABLED
4026 NOTUSED X
4027 COMMBAUDRATE R/W 0 = 1200,1 = 2400,2 = 4800,3 =9600
4028 MODBUSID R/W
4029 CURRENTLYCONTROLLING R 0=NO,1=YES
4030 SPIADDR R/W
4031 MODICONFLOATFORMA
T
R 0=NO,1=YES
4032 COMMTYPE R/W
0 = NONE,1 = MODBUS,2 = SPI,3=PVREXMIT,
4=HANDHELDDISPLAY
4033 COMP2ENABLED R 0=DISABLED,1=ENABLED
4034 HEATCOOLSWITCHDELAY R
4035 DACOUTPUTSPI0 R 16bitvaluebeingsenttoDACcard
4036 DACOUTPUTSPI1 R 16bitvaluebeingsenttoDACcard
4037 DACOUTPUTCOMM R 16bitvaluebeingsenttoDACcard
4038 PIDOU
T
R ‐100to100PIDalgorithmoutput
4039 MODBUSCOMMAND R/W 0=DoNothing,1=Start,2=Stop
4040 EXTENDEDRANGEENABLED R 0=DISABLED,1=ENABLED
ModBusParity=None,StopBits=1