User guide

Corporate Office: 724.584.5500 Instant Access 24/7 (Parts and Service): 800.458.1960 Parts and Service: 814.437.6861
32
Table5ControllerControlFaultLogic
Fault
Alarm
Indication
Pump
Shut
Off
Compressor
ShutOff
Alarm
Reset
Required
1
Manual
Reset
Required
2
Remote
Alarm
Activated
3
LowReservoir
Level
TheReservoirLevelLightflashes
red
Yes Yes Yes Yes Yes
Temperature
LimitSafety
TheSetpointandActual
TemperaturesFlashandthe
TemperatureLimitLightflashes
red
Yes Yes Yes No Yes
Temperature
LimitWarning
TheTemperatureLimitLight
flashesyellow
No No Yes No Yes
PumpMotor
Overload
ThePumpLightflashesred
Yes Yes Yes Yes Yes
Compressor
MotorOverload
TheCompressorLightflashesred
No Yes Yes No Yes
HighRefrigerant
Pressure
TheHighRefrigPressureLight
flashesred
No Yes Yes Yes Yes
LowRefrigerant
Pressure
TheLowRefrigPressureLight
flashesred
No Yes Yes No Yes
LowEvaporator
Temperature
TheFreezestatLightflashesred
No Yes Yes No Yes
SupplyProbe
FaultHi
TheSetpointTemperatureDisplay
shows“PRS”andtheActual
TemperatureDisplayshows“EHi”
Yes Yes Yes No Yes
SupplyProbe
FaultLo
TheSetpointTemperatureDisplay
shows“PRS”andtheActual
TemperatureDisplayshows“ELo”
Yes Yes Yes No Yes
ReturnProbe
FaultHi
TheSetpointTemperatureDisplay
shows“PRR”andtheActual
TemperatureDisplayshows“EHi”
Yes Yes Yes No Yes
ReturnProbe
FaultLo
TheSetpointTemperatureDisplay
shows“PRR”andtheActual
TemperatureDisplayshows“ELo”
Yes Yes Yes No Yes
Freezestat
ProbeFaultHi
TheSetpointTemperatureDisplay
shows“FRR”andtheActual
TemperatureDisplayshows“EHi”
Yes Yes Yes No Yes
Freezestat
ProbeFaultLo
TheSetpointTemperatureDisplay
shows“FRR”andtheActual
TemperatureDisplayshows“ELo”
Yes Yes Yes No Yes
Brownout TheSetpointTemperatureDisplay
shows“Brn”andtheActual
TemperatureDisplayshows“Out”
Yes Yes Yes No Yes
3PhasePower
Error
TheElectricalPhaseErrorlist
flashesred
Yes Yes Yes No Yes
LowFlow TheLowFlowLightflashesred Yes Yes No No Yes
1
AlarmSilence/Resetbuttononcontrolpanelmustbepressed.
2
Safetycontroldevicemustbemanuallyresetbeforethecontrollercanbereset.
3
Activatesthealarmhornandclosesthealarmcontactiftheremotealarmcontactoptionhasbeenpurchased.
