Table 4 - Controller Program Menu
ItemName ItemCode DefaultValue Range
AlarmDelay‐HighDeviation AdH 30 10to60
AlarmDelay‐LowDeviation AdL 30 10to60
AutostartEnabled ASE DIS Disabled(DIS)orEnabled(EnA)
BrownoutEnabled brn EnA Disabled(DIS)orEnabled(EnA)
CommBaudRate bAU 96 12to96
CommModbusID id 1 1to247
CommSPIAddress SPA 32 32to63
CommunicationsType COt OFF OFF,Retransmit(rEt),SPI(SPI)orModBus(bUS)
Compressor1NegativeSpread nS1 4 1to10
Compressor1PositiveSpread PS1 2 1to10
Compressor2Enabled CO2 DIS Disabled(DIS)orEnabled(EnA)
Compressor2NegativeSpread nS2 5 1to10
Compressor2PositiveSpread PS2 3 1to10
Derivative dEr 3 0 to200
DisplayUnits Unt F FtoC
FreezestatLimit FSL 40 50to40
HighDeviationAlarmLimit HId 10 5to100
Integral Int 25 1to800
LowDeviationAlarmLimit Lod 10 5to100
ProportionalBand bnd 8 1to300
RemoteSetpointHighLimit rSH 65 BetweenrSLand999
RemoteSetpointLowLimit rSL 20 Between‐99andrSH
RemoteSPEnabled rSE DIS Disabled(DIS)orEnabled(EnA)
RetransmitRangeHigh rEH 150 Between999andrEL
RetransmitRangeLow rEL 0 Between‐99andrEH
UserHighSafetyLimit HSU 140 Betweenfactorylowandhighlimits
UserLowSafetyLimit LSU 10 Betweenfactorylowandhighlimits
UserPassword UPA 000 0to999