User guide

Corporate Office: 724.584.5500 Instant Access 24/7 (Parts and Service): 800.458.1960 Parts and Service: 814.437.6861
26
DownButton
TheDownArrowbuttondecreasesthesetpointtemperature.PressingtheDownArrowand
releasingitdecreasesthesetpointtemperaturebyonedegree.PressingtheDownArrow
buttonandholdingitdecreasesthesetpointtemperatureuntilreachingtheminimum
allowablesetpointtemperature.Inadditiontoadjustingthesetpointtemperature,theDown
Arrowbuttonadjustsvariousalarmsandsetpointvalueswhentheunitisintheprogramming
mode.
ControlPowerOnLED
TheControlPowerlightisonandgreenwhentheControlPowerSwitchisintheONposition
and24VDCcontrolvoltageispresent.
AutostartSignalLED
TheAutostartSignallightisonandyellowwhentheAutostartfunctionisenabledandno
Autostartsignalispresent.ItisonandgreenwhentheAutostartfunctionisenabledandthe
signalispresent.Thisfeatureallowstheunittobeturnedonandoffbyaremotecontact
closure.SwitchingthecontactsfromopentoclosesimulatespressingtheStartbuttononthe
controlpanel.SwitchingthecontactsfromclosedtoopensimulatespressingtheStopbutton.
Fromthefactory,theAutostartfeatureisdisabled.SeetheProgramMenusectionfor
instructionsonhowtoenableordisabletheAutostartfeature.
Warning:Donotintroduceanyexternalvoltagetothesecontacts,asthiswillresultindamageto
themicroprocessor.
PumpLED
ThePumpLEDissolidgreenwhileinnormalrunningoperation.Itwillflashrediftheoverload
safetytrips.
HotGasBypassLED
TheHotGasBypassLEDwillpulseorbeilluminatedsolidlywhenthechillerisoperatingat
partialload.Underpartialload,thehotgasbypassvalveisopenedinorderforthechillerto
maintainaconstantToProcesstemperature.Thehotgasbypassvalveopenstoavariable
percentage.
TheLEDindicatesanapproximateopeningpercentagebypulsingforvarying
amountsoftime.IftheLEDisilluminatedfor5seconds,thatmeansthatthevalveisopen50%,
whileifitisopenedfor10seconds,itisopen100%.ThelongerthatthisLEDstayson,themore
unusedexcesscapacityisavailablefromthechiller.IfthePartialLoadLEDstaysoff,thechiller