User guide
Corporate Office: 724.584.5500 Instant Access 24/7 (Parts and Service): 800.458.1960 Parts and Service: 814.437.6861
10
flowratemustchangeatarateofnogreaterthan10%perminuteinordertomaintainan
acceptableleveloftemperaturecontrol.Thisisapracticalamountofwaterwhichtypically
buffersfluctuationsintheprocessenoughthatthechillerwillgenerallyseefairlygradualrates
ofchange
intheinletwatertemperatureandwillbeabletoaccuratelyloadorunloadthe
compressor(s)whichinturnwillallowforveryconsistentandstablesupplytemperaturestothe
process.Useasystemvolumeof6to10gallonsofcoolantperton(6.4to10.8LperkW)if
the
flowratechangesmorerapidlythan10%perminute.Ifthechillerseesanetrateofchange
greaterthan10%perminuteitmayresultintemporarysupplytemperaturefluctuations
greaterthan1°F(0.5°C).
Table 2 – Chiller Flow Rate Limitations
ChillerModel
MinimumFlow NominalFlow MaximumFlow
gpm(lpm) psi(kPA) gpm(lpm) psi(kPA) gpm(lpm) psi(kPA)
EP2A‐04 4.9 (18.5) 1.5(10.2) 9.7(36.7) 5.8(40) 19.6(74.2) 23.8(163.8)
EP2R‐04 4.9(18.5) 1.5(10.2) 9.7(36.7) 5.8(40) 19.6(74.2) 23.8(163.8)
EP2A‐05 5.9 (22.1) 1.9(13) 11(41.6) 6.6(45.5) 23.4(88.6) 29.7(204.4)
EP2R‐05 5.9(22.1) 1.9(13) 11(41.6) 6.6(45.5) 23.4(88.6) 29.7(204.4)
EP2A‐08 8.6 (32.4) 1.6(11.2) 16.8(63.6) 6.2 (42.7) 34.2(129.4) 25.7(176.9)
EP2R‐08 8.6(32.4) 1.6(11.2) 16.8(63.6) 6.2(42.7) 34.2(129.4) 25.7(176.9)
EP2A‐10 12.8(48.4) 2.7(18.3) 24(90.8) 9.3(64.1) 51.2(193.8) 42.4(292.4)
EP2R‐10 12.8(48.4) 2.7(18.3) 24(90.8) 9.3(64.1) 51.2(193.8) 42.4(292.4)
EP2A‐13 14.7(55.6) 2.4(16.5) 26.7(101.1) 7.9(54.5) 58.8(222.6) 38.4(264.4)
EP2A‐15 17.3(65.5) 2.1(14.7) 32.1(121.5) 7.4(51) 69.2(261.9) 34.2(235.9)
EP2R‐15 17.3(65.5) 2.1(14.7) 32.1(121.5) 7.4(51) 69.2(261.9) 17.3(65.5)
EP2A‐20 23(87.1) 2.5(17) 43.4(164.3) 8.8(60.7) 92(348.2) 39.5(272.5)
EP2R‐20 23(87.1) 2.5(17) 43.4(164.3) 8.8(60.7) 92(348.2) 23(87.1)
EP2A‐25 29.2(110.4) 1.9(13.3) 54.5(206.3) 6.7(46.2) 116.6(441.5) 30.8(212)
EP2R‐25 29.2(110.4) 1.9(13.3) 54.5(206.3) 6.7(46.2) 116.6(441.5) 30.8(212)
EP2A‐30 34.6(130.8) 2.2(15.4) 64.3(243.4) 7.7(53.1) 138.2(523.2) 35.7(245.7)
EP2R‐30 34.6(130.8) 2.2(15.4) 64.3(243.4) 7.7(53.1) 138.2(523.2) 35.7(245.7)
EP2A‐35 40(151.2) 1.9(13) 94.5(357.7) 10.6(73.1) 159.8(605) 30.2(208.2)
EP2R‐35 40(151.2) 1.9(13) 94.5(357.7) 10.6(73.1) 159.8(605) 30.2(208.2)
EP2A‐40 45.4(171.7) 2(14.1) 104.8(396.7) 10.9(75.2) 181.4(686.8) 32.6(225)
EP2R‐40 45.4(171.7) 2(14.1) 104.8(396.7) 10.9(75.2) 181.4(686.8) 32.6(225)
EP2W‐05 6.4(24) 2.2(15.3) 12.7(48.1) 8.7(60) 25.4(96.1) 35(240.8)
EP2W‐08 9.2(34.8) 1.9(12.8) 18.5(70) 7.5(51.7) 36.8(139.3) 29.7(204.8)
EP2W‐10 14(53) 3.2(21.9) 27.6(104.5) 12.3(84.8) 56(212) 50.8(349.8)
EP2W‐15 18.7(70.8) 2.5(17.2) 36.9(139.7) 9.7 (66.9) 74.8(283.1) 40(275.6)
EP2W‐20 25(94.6) 2.9(20.1) 50.3(190.4) 11.8(81.4) 100(378.5) 46.7(321.9)
EP2W‐25 31.5(119.2) 2.2(15.5) 62.8(237.7) 8.9(61.4) 126(476.9) 35.9(247.5)
EP2W‐30 37.2(140.8) 2.6(17.8) 74.3(281.3) 10.3(71) 148.8(563.2) 41.3(284.8)
EP2W‐35 42.7(161.6) 2.2(14.9) 86.3(326.7) 8.8(60.7) 170.8(646.5) 34.5(237.9)
EP2W‐40 47.6(180.2) 2.2(15.5) 95.8(362.6) 9.1(62.7) 190.4(720.7) 36(247.8)