User guide
Corporate Office: 724.584.5500 Instant Access 24/7 (Parts and Service): 800.458.1960 Parts and Service: 814.437.6861
5
foulingbycontaminantsinthecondenserwaterstreamoccurs,performanceisnegatively
affected.Inordertoreducemaintenancecostsandchillerdowntime,awatertreatment
programishighlyrecommendedforthecondensercoolingwater.Ifcondenserpluggingoccurs,
contactourCustomerServiceDepartmentforassistanceintheproperprocedurefor
cleaning
outthecondenser.
Caution:Theuseofuntreatedorimproperlytreatedwaterinachillercanresultinscaling,erosion,
algae,orslimebuildup.Thiscanleadtopoorsystemperformanceorprematurefailure.
Thestandardcoolingcapacityassumes85°F(29°C)condensercoolingwatersupply.Under
normaloperatingconditions,therewillbeapproximately10°F(6°C)risethroughthecondenser
resultingin95°F(35°C)exitingwatertemperaturefromthecondenser.Toensureproperwater
flowthroughthecondenser,thecondenserwaterpumpmustbeabletosupplythepressure
dropgiven(seeFigure1orFigure2onthefollowingpages)whenprovidingtherequired
condenserwaterflowasshowninTable1.Whilethedesignpressurelossismuchlowerthan
25PSI(1.75Kg/cm
2
),werecommendthepumpingsystembesizedforthislosstoensurethere
willbesufficientsupplypressuretothecondensers.Topreventdamagetothecondenseror
regulatingvalve,thecondenserwaterpressureshouldnotexceed150PSIG(10.5Kg/cm
2
).The
condenserwaterregulatingvalvecontrolsthecondenserwaterflow.Thechillerloadingand
condenserwaterinlettemperaturedeterminetheactualflow.Thecondenserwatersupply
temperaturerangeisfrom70°F(21°C)to90°F(32°C).Supplytemperaturesoutsidethisrange
arenotrecommendedandmayleadtoimproperchilleroperation.
Thewaterregulating
valvewillmodulatethe
flowrateofcondenser
waterthroughthe
condenserinorderto
maintainthedischarge
pressuresetpoint.Ifthe
dischargepressureis
abovethesetpoint,the
water‐regulatingvalve
willopentoincrease
thewaterflowattemptingtoprovidemorecooling.Thecondenserwater
flowcanexceed
nominalflowratesduringtheseconditionsandreducetheavailablewaterflowthroughother
processesifsharingthesamepump.
Warning:Ifthecondenserwaterpumpisfeedingothersourcesinadditiontothechiller,itishighly
recommendedtoinstallanappropriatebalancevalveinlinewiththechillerinordertolimitthe
maximumflowthroughthechiller.
Table 1 – Water Cooled Condenser Water Flow Rate Requirements
ChillerModel
NominalFlow
gpm(lpm) psid(kPA)
EP2W‐05 16.5(62.5) 15.4(106.1)
EP2W‐08 24.1(91.2) 13.6(93.7)
EP2W‐10 35.8(135.5) 29.4(202.6)
EP2W‐15 48(181.7) 23.2(159.8)
EP2W‐20 64.9(245.7) 11.1(76.5)
EP2W‐25 81.7(309.3) 9.5(65.5)
EP2W‐30 96.4(365) 18.2(125.4)
EP2W‐35 111.6(422.5) 27.3(188.1)
EP2W‐40 124.3(470.6) 30.6(210.8)