Specifications

A ppendix l AA-23
DRYER MAIN MENU
STAT SETUP DIAG
DRYER STATUS
PROC REGEN OTHER
DRYER OTHER
STATUS SCREENS
PANEL INSIDE TEMP
ACT 100
˚
F
DM T6 TOP
ACT 150 F
DM T5
ACT 155 F
DM T4
ACT 158 F
DM T3
ACT 160 F
DM T2
ACT 163 F
A
A
A
A
A
Screen References
From Dryer Control
Flow Chart
DM T1 BOTTOM
ACT 165 F
DM PROCESS SETPOINT
SET 225 F
DM LO ALARM SELECT
TEMPERATURE T4
DM LO ALARM SETPOINT
SET 150 F
DM LO ALARM OFFSET
SET 10 F
A
M
B
C
D
DM LO ALARM BAND
SET 40 F
DM LO ALARM DELAY
SET 5 MIN
DM LO ALARM SETPOINT
HIGH LIMIT 170 F
DM LO ALARM SETPOINT
LOW LIMIT 130 F
DM TEMP NOT MET
ALARM TIME SET 4 HRS
E
F
G
H
I
DM-II Control
Functions
Operator
Mode
Screen only present
if configured for a
central dryer.
View/Monitor Only (Changes can not be made on these
screens.)
NOTE: All other screens
require the supervisor
password.
NOTE: Due to tolerances of RTD’s it would
not be uncommon to see a probe with a
temperature that is higher located further
up in the hopper. For example, T4 with an
actual temperature of 164°F and T3 with
an actual temperature of 159°F.