Specifications

68
9 Troubleshooting
9.2 Error indication
Malfunctionsduringoperationareindicatedbyacorrespondingwarningmessage(operationstillpos-
sible,redLEDashes)orafaultmessage(operationnotpossibleanylonger,redLEDlights)inthe
display of the operating and control unit. Detailed information thereto can be found in the separate
operating instructions for Condair GS control.
9.1 Importantnotesontroubleshooting
Qualicationofpersonnel
Have faults eliminated by adequatelyqualiedandtrainedpersonnel only. Malfunctions caused by
theelectricalinstallationmustberepairedbyauthorizedpersonnel(e.g.electrician)only.
Safety
When eliminating faults, the Condair GS mustbetakenoutofoperation, as described in chapter
7.5, and prevented from further inadvertent operation.
Make sure the power supply to the unit is cut off (test with voltage tester) and that the stop
valves in the water and gas supply line are closed.
General note
Most operational malfunctions are not caused by faulty equipment but rather by improper installa-
tionordisregardingofplanningguidelines.Therefore,acompletefaultdiagnosisalwaysinvolvesa
thoroughexaminationoftheentiresystem.Often,thesteamhoseconnectionhasnotbeenproperly
executed,orthefaultlieswiththehumiditycontrolsystem.
9.3 Resetting the error indication
To reset the error indication:
DisconnecttheCondairGSfromthemainsforapprox.5seconds,thenreconnectagain.
Note:Ifthefaulthasnotbeeneliminated,theerrorindicationreappearsafterashortwhile.