6 Inspecting the installations (Check list)
BeforetheCondairGSisoperatedforthersttime,theresponsiblepersonnelmustinspect all
installations for correct execution (observing of local regulations)andcheckthattheunit is
correctlycongured.Alldecienciesmustbecorrectedbyspecialistactionbeforecommissioning
takesplace.
Usethefollowingchecklisttoascertainthattheinstallationswereperformedcorrectly:
Unit installation
Is the unit in the correct place (see chapter 5.2.1)?
Is the unit correctly aligned vertically and horizontally?
Issteamhumidierproperlysecured(unitstandxedtotheoor)?
Steaminstallation
Steam distribution pipe
Steamdistributionpipecorrectlypositionedandsecured(screwstightened)?
Aretheoutletoricesatrightanglestotheairowdirection?
– Steampipebetweensteamoutletonunitandsteamhoseadapter(mainsteampipe)
Maximumlengthof6m?
Minimumbendradiusof4-5xinternaldiameterofsolidsteampipe?
Is the pipe properly insulated?
Is the correct installation material used?
Is the minimum internal diameter maintained over the entire pipe length?
– Steamhosebetweensteamhoseadapterandsteamdistributor
Maximumlengthof4m?
Minimumbendradiusof300mm(4-5xinternaldiameterwithxedpiping)?
Havetheinstructionsforhosepositioningbeenfollowed?
Steamhose:nosagging(condensatepocket)?
Rigid steam lines: properly insulated? Correct installation material used? Minimum internal
diameter maintained?
Steamhosesecurelyattachedwithclamps?
Heatexpansionduringoperationandshorteningofthehosewithageingtakenintocon-
sideration?
Condensate hoses
Downslopeofatleast20%?
Siphonsexistingandlledwithwater?
Condensatehosescorrectlyxed?
Water installation
– Fillingwatersupply
Hasltervalve(accessory“Z261”)orshut-offvalveandlter5µmrespectivelybeenin-
stalled in supply line?
Have admissible water pressure (3.0 – 8 bar) and temperature (1–30 °C) been ob-
served?
Doessupplycapacitymatchthehumidier(s)?
Is the piping properly secured and sealed?