Specifications
46
Installation notes
Allworkconcerningtheelectricinstallationmustbeperformedonlybyadequatelyqualiedperson-
nel(electricianorworkmanwithequivalenttraining).Ascertainingthequalicationsisthecustomer‘s
responsibility.
Observe all local regulations concerning the electric installation.
DANGER! Danger of electric shock!
Thesteamhumidiermaybeconnectedtoelectricmainsonlyafterallinstallationworkhasbeen
completed.
CAUTION!
Theelectronicpartsinsidethehumidierareverysensitivetoelectrostaticdischarge.Toprevent
damage,appropriatemeasuresagainstelectrostaticdischarge(ESDprotection)mustbetaken
whencarryingoutinstallationwork
Primarywiring
Humidiersrequireeldwiringtoprimaryvoltageterminalblocks.Powerrequirementis220…240V/50…60Hz,
10Aslow-actingfused(“F1”)circuit,singlephase.Wiringisfedthrougha22mmholeinthebottomofthe
controlcompartment.Installationofexternalserviceswitch“Q”(allpoledisconnectingdevicewithaminimum
contact opening of 3 mm) is mandatory.
Wheninstalled,theappliancemustbeelectricallygroundedinaccordancewithlocalcodes,ifanexternal
electrical source is utilized.
Connectgroundwiretocabinetgroundclamp.
Externalwiringsizesmustbeinaccordancewithexistinglocalelectricalcodesandby-laws.
Remoteoperationandfaultindication(H1)
TheRemoteoperationandfaultindicationboardisequippedwith4relaysforremoteoperationandfault
indication.
– “On”:thisrelayclosesafterthehumidierhasbeenpoweredup
– “Steam”: this relay closes as soon as steam is produced
– “Service”: thisrelaycloseswhenthesetmaintenanceintervalhasexpired
– “Error”: thisrelaycloseswhenanerroroccurs
External safety circuit (K1)
Toguaranteethesafetyofthehumidicationsystem,monitoringtheoperationbymeansofasafetycircuit
isanabsoluterequirement.Toaccomplishthis,thepotential-freecontacts(250V/2A)ofexternalmonitoring
devices(B1:safetyhighlimithumidistat,B2:airowmonitor,B3:ventilationinterlock,etc.)areconnectedin
series to terminals 1 and 2.
Control or sensor signal
The control signal (signal Y) is connected to terminals 3 and 4. The air supply limit signal (signal Z) is con-
nectedtoterminals3and5.BydefaulttheCondairGSisconguredfora0…10VDCcontrolsignals.The
controlsignaltypecanbemodiedviathesoftware(seemenu“usersettings”,intheoperatinginstructions
fortheCondairGScontrol).ThecongurationwhethertheCondairGSiscontrolledviatheinternalorviaan
externalcontrollerisalsodoneviathesoftware.
Output A3
This output is available for custom purposes. The lines are connected to terminals 6 and 7. The output signal
typeisconguredbysettingthejumperonJP3(5Vdcmax.500mA)oronJP4(24Vdcmax.150mA).
Full tank blow down 24 VAC (S1)
Thisinputsignalcanbeusedforremotetriggeringafulltankblowdown.Ifa24VACsignalispresentformore
than60secondsthetankblowsdown.Thesignallineisconnectedtoterminals8and7.