Specifications

37
5.6 Flue gas installation
Important:Since the regulations fortheinstallationofueingsystemsdifferfromcountrytocountry,
therelevantlocalregulationsmustbeadheredtowithoutreservation.
In any case, please consult your Condair representative. Thisappliesinparticulartotheroom
air-independentsteamairhumidiers(RSunits).
Pleasenotethatueingmustbedesignedforoverpressureorunderpressure,dependingonlocal
regulations.
Allworkconcerningtheuepipeinstallationmustbeperformedonlybyadequatelyqualiedperson-
nel.Ascertainingthequalicationsisthecustomersresponsibility.
5.6.1 Performinguegasinstallation
Overview
1 Flue gas connection on the unit
GS 40: ø76 mm (3")
GS 80: ø101 mm (4")
GS 120/GS 160: ø127 mm (5")
GS 200/GS 240: ø152 mm (6")
2 Fluegasadapterwithcondensatedrain(accessory“FA...”)
GS 40: FA40 (D
A
= 80 mm)
GS 80: FA80 (D
A
= 100 mm)
GS 120/GS 160: FA120/160 (D
A
= 130 mm)
GS 200/GS 240: FA200/240 (D
A
= 160 mm)
3 Flue gas pipe (building side)
4 Condensate drain (building side)
5 Siphon (min. diameter 300 mm, building side)
D
A
3
2
1
5
4
max.40mm
ø15 mm
D
A
GS 40 ø80 mm
GS 80 ø100 mm
GS 120 / GS 160 ø130 mm
GS 200 / GS 240 ø160 mm