Specifications
34
5.5 Gas installation
Installation notes
The gas supply pipe must be connected to the connection on the unit via a shut-off valve (essential
requirement),whichisinstalledintheimmediatevicinityoftheunit.Whensteelgaspipesareinuse,
itisessentialthatasedimentseparatorbettedbetweentheshut-offvalveandtheunitconnection.
Thefollowingconnectiondatamustbeadheredto:
– Permissible gas operating pressure:
Gas Operatingpressure(mbar)
Nominal Min Max
Natural gas H, E, E(S) G20 20 17 25
Natural gas L, ELL G25 25 20 30
Natural gas HS G25.1 25 20 30
NaturalgasLw G27 20 17.5 23
Natural gas Ls GZ350 13 10.5 16
Propane gas P G31 37 or 50 25 57.5
– The connection material used must be pressure tested and approved for gas installations.
– Donotuseteontapeongaslinepipethreads.AexiblesealantsuitableforusewithNatural
Gas and Propane Gas is recommended.
– Plangassupplypipingsoitwillnotinterferewithremovalofgasvalvesorblowerassembliesand
front or side service doors.
Allinstallationworkmustbecarriedoutinaccordancewiththe applicable local building and in-
stallation regulations.
5.5.1 Performingthegasinstallation
Overview Gas installation
1 Gas supply connection
Model Connection
GS 40 BSP1/2"
GS 80 BSP3/4"
GS 120 and GS 160 BSP1"
GS 200 and GS 240 BSP11/4"
2 Gas shut-off valve (building side)
3 Sediment trap (Installation - building side -
essential in the case of the use of steel
gas pipes)
3
1
2