Water supply
Thewatersupplypipeistobeconnectedviatheltervalve(accessory“Z261”),totheconnection
ontheunit(seeforegoingillustration).Theltervalveshouldbeinstalledasclosetothehumidier
as possible.
Note:Insteadoftheltervalve,ashut-off valve and a waterlter5µm ( (both essential) can be
used.
Thefollowingspecicationsmustbeobserved:
Connections on unit: BSP 3/4" (outside thread)
Min. inner diameter of supply line: 12mm
Admissible mains pressure 3.0 to 8.0 bar (hammer-free system)
Formainspressures>8bar,connectionmustbemadeviapressurereducingvalve(adjustedto
3.0bar).Formainspressures<3.0barpleasecontactyourCondairsupplier.
Supply rate: 10l/min
Admissible supply temperature: 1…30 °C
Notesonwaterquality:
– ForthewatersupplyoftheCondairGS,useexclusivelyuntreated drinking water or fully
demineralizedwater.
Note:Theuseoffullydemineralizedwaterreducesthemaintenanceandthecleaningofthe
watertanktoaminimum.
The use of additives such as corrosion inhibitors, disinfectants, etc. is not allowed, since
these additives may endanger health and affect proper operation.
– IftheCondairGSshallbeoperatedwithsoftenedorpartlysoftenedwater,pleasecontactyour
Condair supplier.
– Theconnectionmaterialmustbepressure-proofandcertiedforuseindrinkingwatersupply
systems.
CAUTION!
Fullydemineralizedwaterisaggressive.Whenmakingconnectionstoafullydemineralizedwater
system,useexclusivelyplasticorstainlesssteelinstallationmaterials(min.DIN1.4301).
Important!Beforeconnectingthewaterlinetotheunit,thelinemustbeushedthoroughly.