Specifications

30
min. 20 %
min. 300 mm
Ø min. 200 mm
Securing the hose
Thesteamhosemustbesecuredtothesteamdistributionpipeandhumidiersteamoutletbymeans
of hoseclamps.
Steamlinewithxedpiping
Forsteamlineswithxedpiping,thesameinstructionsapplytothelayingofthepipingasalready
described.Thefollowingadditionalnotesshouldbeobserved:
The minimuminternaldiameterof45mmshouldbeappliedoverthewholelengthofthepiping.
– UseexclusivelyCupipe(foroperationwithuntreateddrinkingwateronly)orstainlesssteel(min.
DIN 1.4301).
To minimize the condensate formation (=loss), the steam pipes must be insulated.
The minimumbendradius for solid pipes is 4-5xinternaldiameter.
90°bendsshouldbeavoided.Whereverpossible,tubebendswithlargeradiishouldbeused(e.g.
producedusingatubebendingmachine,orconstructedfromapairof45°bends).Thisreduces
the performance loss due to the formation of condensate, and in addition, the static pressure in
the steam line.
Important!Allowancemustbemadeforapressurelossof10mmwatercolumn(approx.
100 Pa)permeterlengthorper90°bend.
– Connectionofthesteampipestothesteamdistributionpipeandsteamhumidieriseffectedby
meansofshortlengthsofsteamhosesecuredwithhoseclamps.
5.3.4 Installing the condensate hoses
The individual condensate hoses of the main steam pipe (if present), the steam hose adapter (if
present)andthesteamdistributionpipesmustbeleddownwithaminimumdownslopeof20%
via a siphon (min. hose bend ø200 mm) into a discharge funnel.
Important!Beforeputtingtheunitintooperation,thesiphonofthecondensatehosemustbelled
withwater.
Important!UseoriginalCondaircondensatehoseexclusively.Othertypesofhosescancauseoper-
ational malfunctions.