5.3.2 Installingthemainsteampipe
Thesteampipebetweenthesteamoutletoftheunitandthesteamhoseadapter(mainsteampipe)
mustbemadewithsolidpiping.
Thefollowingnotesmustbeobserved:
The internal diameter of the steam outlet on the unit must be maintained over the entire length
of the main steam piping.
– Themaximumlengthofthemainsteampipeis6m.
Important!Allowancemustbemadeforapressurelossof10mmwatercolumn(approx.
100 Pa)permeterlengthorper90°bend.
The minimumbendradius for solid pipes is 4-5 x internaldiameter.90°bendsshould be
avoided.Whereverpossible,pipebendswithlargeradiusshouldbeused(e.g.producedusing
apipebendingmachine,orconstructedfromapairof45°bends).Thisreducestheperformance
loss due to the formation of condensate, and in addition, the static pressure in the steam line.
– UseCupipe(foroperationwithuntreateddrinkingwateronly)orstainlesssteelpipe(min.DIN
1.4301)exclusively.
To minimize the condensate formation (= loss), the steam pipes must be insulated over the entire
length of the piping.
Connection of the steam pipe to the steam outlet on the unit and the connection on the steam
hoseadapteriseffectedbymeansofshortlengthsofsteamhosesecuredwithhoseclamps.
– Atspotswherecondensatecouldaccumulateinsidethepipeacondensatedrainwithsiphon
(min. hose bend Ø200 mm) must be mounted.
Main steam pipe
(max.length6m)
steam hose adapter
(accessory “SA..”)
steam hoses
(max.length4m)
min. 1 m