Specifications
18
OptiSorp Numberofsteam
connections
Max.steamcapacity
in kg/h
1)
Ductdimensions
Widthinmm Heightinmm
System1 1 45 (30) 450...4000 450...1650
System2 2 90 (60) 450...4000 450...2200
System3 3 135 (90) 450...4000 800...3200
System4 4 180 (120) 450...4000 800...3200
1)
Forductwidths<600mmthevaluesinbracketsapply
4.4.2 Accessory details
Steamdistributionpipes
Thesteamdistributionpipesareselectedonthebasisoftheductwidth(forhorizontalinstallation)
ortheductheight(forverticalinstallation)andthecapacityofthesteamhumidier.
Important!Alwaysselectthelongestpossiblesteamdistributionpipe(optimumhumidicationdis-
tance).
Steam distribution pipes
1)
for
GS 40, 80, 120, 160, 200 and 240
Ductwidth(B) Steam capacity
Type Length in mm (L)
2)
in mm max.inkg/h
3)
81-350 350 400…600 30
81-500 500 600…750 30
81-650 650 750…900 50
81-800 800 900…1100 50
81-1000 1000 1100…1300 50
81-1200 1200 1300…1600 50
81-1500 1500 1600…2000 50
81-1800 1800 2000…2400 50
81-2000 2000 2200…2600 50
81-2300 2300 2500…2900 50
81-2500 2500 2700…3100 50
1)
Material: CrNi steel
2)
Special length on request
3)
TofullyexploittheoverallcapacityofyourGShumidier,theoutputofeach
steam outlet may be fed to more than one distribution pipe. If more than one
steam distribution pipe is fed per steam outlet the steam line must be divided
intomultiplebranches.Appropriatettingsareavailableonrequest.
Note:Ifthehumidicationdistance(seechapter5.3.1)hastobereducedfortechnicalreasons,the
steamoutputofyourunitmustbedividedbetweentwosteamdistributionpipes or the OptiSorp
steamdistributionsystem must be used. If this is the case, contact your Condair supplier.
OptiSorpsteamdistributionsystem
TheOptiSorpsteamdistributionsystemisusedinventilationductswithashorthumidicationdistance
(forthecalculationofthehumidicationdistancerefertochapter5.3.1).WhenorderinganOptiSorp
systemtheductdimensionmustbespecied.Pleaseconsultthedatainthefollowingtable.