Specifications

17
4.3 Options
At the moment no options are needed for the Condair GS.
4.4 Accessories
4.4.1 Accessories overview
Model Condair GS 40 ... 80 ... 120 ... 160 ... 200 ... 240 ...
Steamdistributionpipe
(see accessory details in chapter 4.4.2)
81-...
number 1 2 3 4 5 6
OptiSorpsteamdistributionsystem
(see accessory details in chapter 4.4.2)
System1 System2 System3 System4 System2
System3
System3
number 1 1 1 1 1 of each 2
Steamhoseadapter ––– SA80
(3"/2x13/4")
SA120
(3"/3x13/4")
SA160
(4"/4x13/4")
SA200
(4"/6x13/4")
SA240
(4"/6x13/4")
number ––– 1 1 1 1 1
Steamhose/meter DS80
number 1 2 3 4 5 6
Condensatehose/meter KS10
number 1 2 3 4 5 6
Filter valve Z261 (1 pc. per system)
Flue gas adapter with
condensate drain
FA40 FA80 FA120/160 FA200/240
number 1 1 1 1
Control/input signals
TheCondairGSisregulatedviatheinternalPIDcontrolleroranexternalcontinuouscontroller(e.g.
PI controller).
Important!Forthecontrolsystems2and3theexternalcontrollermustbeequippedwithtwocontrol
signal inputs.
TheCondairGSprocessesthefollowingcontrolsignals:
0 ... 10 VDC
2 ... 10 VDC
0 ... 10 mADC
2 ... 10 mADC
0 ... 20 mADC
4 ... 20 mADC
0 ... 5 VDC
1 ... 5 VDC
Further information is provided in Chapter 5.9.
Output signals
TheCondairGSprovidesthefollowingoutputsignals:
– 10VDC(max.20mA)
Remote operating and fault signals (4 potential-free contacts)
Further information is provided in Chapter 5.9.