– System3:Supplyairhumiditycontrolwithcontinuousoutputlimitation
Supply air humidity control (humidity sensor installed in supply air duct) should be used only
whereroomhumiditycontrolisimpracticablefortechnicalreasons.Suchsystemsalwaysrequire
a PI-controller.
The humidity sensor (A1) is located in the supply air duct after the steam distribution pipe. The
humidity sensor (A2) for the continuous output limitation is located in the supply air duct before
thesteamdistributionpipe.SuchasystemrequirestheinternalPIDcontrolleroranexternalPI-
controllerwiththeoptiontoconnectasecondhumiditysensor.
A1/2 humidity sensor
B1 ventilationinterlock
B2 airowmonitor
B3 safetyhumidistat
PI
E
externalPI-controller
PID
I
internal continuous controller (PID controller)
Y input signal from A1
Z input signal from A2
Whichhumiditycontrolsystemforwhichapplication?
Application Locationofthehumiditysensor
Roomorexhaustairduct supply air duct
Airconditioningsystemswith:
Supply air portion up to 33% System 1 System 1
Supply air portion up to 66% System 1 or 2 System 2 or 3
Supply air portion up to 100% System 2 System 3
Supply air humidity control ––– System 3
PleasecontactyourCondairsupplier,ifyourapplicationmeetsthefollowingconditions:
– Humidicationofsmallroomsupto200m
3
– Airconditioningsystemswithahighnumberofairexchanges
– Systemswithvariableairvolumeow
– Testfacilitieswithextremecontrolaccuracyrequirements
– Roomswithahighvariationinmax.steamcapacity
– Systemswithtemperatureuctuations
– Coldroomsandsystemswithdehumidication