Specifications
15
4.2 Selectingthecontrolsystem
Thevariouscontrolsystems
– System1:Roomhumiditycontrol
System1issuitedforairconditioningsystemswithmainlyrecirculatedair.Thehumiditysensor
ispreferablylocatedintheroomitselforintheexhaustairduct.
A1/2 humidity sensor
B1 ventilationinterlock
B2 airowmonitor
B3 safetyhumidistat
PI
E
externalcontinuouscontroller(e.g.PIcontroller)
PID
I
internal continuous controller (PID controller)
Y input signal from A1
Z input signal from A2
A1 humidity sensor
B1 ventilationinterlock
B2 airowmonitor
B3 safetyhumidistat
PI
E
externalcontinuouscontroller(e.g.PIcontroller)
PID
I
internal continuous controller (PID controller)
Y input signal from A1
– System2:Roomhumiditycontrolwithcontinuouslimitationofthesupplyairhumidity
System2issuitedforairconditioningsystemswithalargeportionofsupplyair,lowsupplyair
temperature,post-humidication,orvariableairowvolume.Ifthesupplyairhumidityexceeds
the preset value, the continuous limitation is effected prior to the room hum idity control.
Thehumiditysensor(A1)ispreferablylocatedintheexhaustairductorintheroomitself.The
humidity sensor (A2) for the limitation of the supply air humidity is located in the supply air duct
after the steam distribution pipe. This control system requires the internal PID controller or an
externalcontinuouscontrollerwiththeoptiontoconnectasecondhumiditysensor.
Attention! The continuous limitation of the supply air humidity is no substitute for the safety -
humidistat.