Specifications
14
Importantnotes:
– Therequiredmaximumsteamcapacitydependsonthespecicapplicationandtheinstallation.
Thecalculatedsteamcapacitybasedontheaboveformulas,theh,xdiagramandtheconditionof
theairtobehumidieddoesnotconsideranysteamloss(e.g.duetocondensationinthesteam
hosesandthesteamdistributors),anyheatlossoftheunitaswellasanyabsorptionorrelease
ofhumidityofmaterialslocatedintheroombeinghumidied.
In addition, the calculated steam capacity does not consider any losses caused by the draining
ratedependingonthewaterquality.
Thetotalamountoflossesdependsontheentiresystemandmustbetakenintoconsideration
whencalculatingtherequiredsteamcapacity.Ifyouhaveanyquestionsregardingthecalculation
of the steam capacity please contact your Condair supplier.
– Forsystemswherethemax.requiredsteamcapacityvariesextensively(e.g.fortestfacilitiesor
forsystemswithvariableairvolumeow,etc.),pleasecontactyourCondairsupplier.
4.1.2 Combustiongas
TheCondairGScanbeoperatedwithnatural gas or propane.Theequipmentisconguredex-
worksfortherespectivecombustiongasthatistobeemployed.Ifrequired,theequipmentcanbe
convertedatalaterdatetoworkwithoneoftheothercombustiongas.
Combustion gas Designation
Natural gas H, E, E(S) G20
Natural gas L, ELL G25
Natural gas HS G25.1
NaturalgasLw G27
Natural gas Ls GZ350
Propane gas P (Liquid gas) G31
Condair GS 80 C G20 RS
4.1.3 Combustionairsupply
Toensurecorrectcombustion,caremustbetakentoprovideeitheraventilation opening in the
roomwheretheequipmentisinstalled(roomair-dependentdevice) or a separate air inlet pipe
(roomair-independentdevice) so that an adequate supply of clean, fresh air, is available.
Equipment version Designation
Roomair-dependentdevice
Forrooms witha sufcientlylarge ventilationopening
andasourceofcleanintakeair.
Caution! Local building regulations must be observed.
___
Roomair-independentdevice(RSequipment)
Air supply through a separate pipe from outside the
building.Forclosedrooms,roomswithlowairpressure
androomswithdirtyintakeair.
RS
Condair GS 80 C G20 RS