Technical information
UGH024/1103 Portable Chillers
TROUBLESHOOTING
6-7
TIC C
ONTROL
PROBLEMS
Symptom
The control is lit and
there is no alarm
condition. The com-
pressor hums, but
does not run.
Possible cause
The input voltage is
incorrect
There is a phase loss.
Solution
Check the main supply volt-
age. It must be within 10% of
the nameplate rating.
p Check the fuses on the
main power supply.
p Check the phase-to-phase
voltages.
p Check phase continuity
through the compressor con-
tactor.
p Check the wiring at the
compressor.
Replace or repair as needed.
Look here when the Alarm/Shutdown light on the control
panel is lit. See Answering an Alarm, in the Troubleshooting
section before going to these tables.
Alarm
Flow fault (pump
and compressor are
off)
TIC C
ONTROL
ALARM
C
ONDITIONS
Possible cause
Water level in tank is low.
Solution
Fill tank to proper level. See
Checking Reservoir Level, in
the Maintenance section.
Inspect for leaks in the process
piping. Repair as necessary.
See Making Plumbing
Connections, in the Installation
section.