Technical information
Portable Chillers UGH024/1103
6-6 TROUBLESHOOTING
TIC CONTROL
PROBLEMS
Look here if the control panel is not lit, or if the power is on
and the Portable Chiller will not run.
Symptom
The control is not lit
and the chiller is not
working.
Possible cause
Power is not reaching the
chiller.
The correct power is not
reaching the unit
There is a problem with
the TIC control.
There is a problem with
the control panel.
Solution
p Check the power cord and
plug. Make sure the cord and
plug are properly connected.
p Make sure the main dis-
connect switch is on.
p Check fuses and breakers.
Replace or reset as required.
Check the voltage specifica-
tion on the chiller nameplate.
p Check fuses and replace
as needed.
p Check the power to the
temperature controller.
Reconnect or replace as need-
ed.
p Check the TIC indicator
lights and replace as needed.
The control panel may have
failed. Contact Conair Service.