Technical information
4-32 OPERATION
Portable Chillers UGH024/1103
PLC CONTROL
SELECTING PID
VALUES
The PID values are set at the factory to default settings. The
values should be changed only if the water regulator valve or
the VFD are unable to maintain discharge pressure. To set the
discharge pressure setpoints from the main screen:
Press the Setup arrow.
Press the Scroll arrows to scroll through the
Setup screens. Stop when you get to the PID Reset
screen.
2
1
STATUS SETUP RUN ALM
Press arrow
PID Reset DPS FANS
Press arrow
Press the PID Reset arrow.
The PID values for Gain and Reset time display. The gain
is dimensionless (i.e. has no units) and the integral value,
or Reset time, is measured in seconds. There are no upper
or lower limits for these settings.
3
Press Gain: 5
Press Reset: 180 S
Use the Select Values buttons to change the gain and reset.
Press the Enter button to accept the
new value. If the PID values need to be restored to
the factory default settings scroll to the Reset Factory PID
screen from the Setup screen.
4
Reset Factory PID
Press arrow
Press the Reset arrow. Gain restores to 2 and Reset
restores to 180 seconds.