Technical information

OPERATION 4-17
Plug in the power cord to restore power after any required
maintenance. The chiller requires 15 minutes warmup time
after it is plugged in for the crankcase heater to warm up.
Turn on the main power.
The chiller control automatically performs its bootup rou-
tine. The screen displays the Portable Chiller model num-
ber along with the serial number
PLC C
ONTROL
POWERING
U
P
Portable Chillers UGH024/1103
Press the Scroll arrow to move to the
Main screen.
Conair Chiller
PCW - 30 123456
1
2
STATUS SETUP RUN ALM
The main screen displays:
The main screen lets you:
l view the status of the water level, process tempera-
ture, process setpoint, suction pressure, percent glycol,
low temperature cutout and discharge pressure.
l view and change the setups for temperature setpoint,
Autotune mode, high temperature deviation, and per-
cent glycol solution
l run or stop the chiller
l view alarm information
l perform maintenance with password clearance
Press the arrow pointing to the selection
you want displayed on the screen.
STATUS SETUP RUN ALM
Choose a selection
3
XXXXXX
6-digit factory assigned
serial number
PCA or PCW
identifies Air-cooled or
Water-cooled model
30
nominal tonnage