Technical information
OPERATION
4-13
UGH024/1103 Portable Chillers
TIC C
ONTROL
CHANGING
THE
DEVIATION
FROM
SETPOINT
TEMPERATURE
(DT)
Press the Enter key until the default con-
figuration page Un appears on the screen.
Toggle up/down buttons until display
flashes dt, press “Enter”. Use the up/down
buttons to set your desired deviations setpoint tem-
perature.
Press the Mode/Enter button, to accept the
new setpoint temperature.
3
2
This is the temperature value that the actual temperature can
be away from the setpoint. If the actual temperature is more
than the deviation value away from the setpoint the Dtt will
initiate and a passive alarm dtA will occur 300 seconds later.
1
TIC C
ONTROL
CHANGING
THE
ALARM
A
CKNOWLEDGE
TIMER (AAT)
The Alarm Acknowledge timer (AAT) sets the time that an
alarm can be acknowledged and silence without being satis-
fied. The default value of this parameter is 0 minutes. In this
case the alarm silence does nothing and alarms can only be
cleared after the alarm condition is nullified. The range of
times that can be programmed is 0-60 minutes.
Press the Enter key for 5 seconds to show
the default configuration page UN.
Toggle up/down keys until until AAT flash-
es on the display
Press Enter and use the up/down keys to
select your desired amount of time.
NOTE: In the vary rare case that none of these
settings provide adequate control, please consult
the Conair service to further adapt these variables.