Technical information
The low limit temperature alarm setpoint is the setpoint that
protects the chiller from undershooting past the required
process water temperature. The range for this setting is 19.4-
79 and the default is 39. For most applications this value will
need set about 3°F below the LTS value.
Press Menu button until UN is displayed.
Press Enter again to display value of Low
Limit Setpoint to raise and lower the low limit-
setpoint temperature. Each time you press the arrow
the temperature changes one unit. Stop when you
reach the temperature you want.
Press the Enter button, to accept the new set-
point temperature. The display returns to the actual
process temperature.
This feature will indicate when the chilled water system tem-
perature is above an acceptable level. This alarm will be indi-
cated by a flashing HtA. This is not a shutdown alarm only a
indicator. The setpoint range is 50-95 and the default is 85°F
which should be adequate for most applications.
Press Menu button until UN is displayed.
Toggle up/down key until HtA flashes on
the display.
Press Enter and use the up/down keys to
select your desired amount of time.
Press Enter to accept the units.
The High temperature safety is the highest temperature the
process water temperature can get before a shutdown. If shut-
down occurs it will be indicated by a flashing (THS). Range
for this parameter is 75-95 and default value is 95°F.
Press Menu button until UN is displayed.
Toggle up/down key until HtS flashes on
the display.
Press Enter and use the up/down keys to
select your desired amount of time.
Press Enter to accept the units.
1
2
3
Portable Chillers UGH024/1103
4-12 OPERATION
TIC CONTROL
CHANGING
THE LOW
TEMPERATURE
ALARM SETPOINT
(SPL)
TIC CONTROL
SETTING THE
HIGH TEMPERA-
TURE ALARM
(HTA)
1
2
3
4
TIC CONTROL
SETTING THE
HIGH TEMPERA-
TURE SAFETY
(HTS)
1
2
3
4