Technical information

UGH024/1103 Portable Chillers
INSTALLATION
3-15
STATUS SETUP RUN ALM
press arrow
The Run screen displays:
RUN STOP PUMPDOWN
Press the RUN arrow.
Verify that the chiller begins to run. Check that the
Compressor lights and the Process Pump light on the con-
trol panel are lit.
If you get an alarm message on the display:
If you get a Compressor 1, 2 Rotation Error message,
press the Stop Chiller button, unplug chiller from main
power supply, switch any two incoming main power
leads, and apply main power supply. Wait for the required
warmup time and then press Run arrow.
Press the Escape/Previous button to
return to the Main screen.
3
2
4
press arrow
Only after you have checked for leaks and checked for pump
rotation should you run the chiller. To initially run the chiller,
from the main screen:
Press the Run arrow.1
PLC C
ONTROL
INITIALLY
RUNNING
THE
CHILLER