Technical information
Portable Chillers UGH024/1103
3-12 INSTALLATION
PLC CONTROL
INITIALLY
WARMING THE
CHILLER
Turn on main power source.
The control boots up and when finished, the screen dis-
plays the Portable Chiller model number and the six-digit
serial number.
1
Conair Chiller
PCW - 30 123456
WARNING: Initial startup
Do not press any buttons after initially applying
power to the chiller. Let the chiller set, undis-
turbed, for a minimum of 8 hours before starting
the chiller. This is necessary to allow the
crankcase heater to warm properly, and to pre-
vent the refrigerant from pooling in the com-
pressor.
Press the Start Chiller button.
Check the Pump and Compressor lights on the control
panel; they should turn on and off as the pump and com-
pressor cycle on and off. The To Process temperature dis-
plays on the control. The To Process temperature is real-
time temperature. It should change as the chiller runs and
cools the fluid.
After starting the chiller, you need to check pump rotation, the
compressor, and the sight glass. If the chiller is not working
properly at any time, press the red Stop button to turn off the
chiller.
2