Technical information
CHECKING
ELECTRICAL
CONNECTIONS
Portable Chillers UGH024/1103
3-10 INSTALLATION
Open electrical enclosure.*
Check the short-to-ground with an ohm meter.
Connect the ohm meter to each of the three terminal
screws and to the grounding lug. Test all three for resis-
tance. The minimum resistance to ground should be 1
megohm. If it resistance is less that 1 megohm there is a
leak in the system.
WARNING: Electrical hazard
Before performing any work on this item, dis-
connect and lock out electrical power sources to
prevent injury from unexpected energization or
startup.
1
2
Grounding lug
Close the electrical enclosure.
The chiller is now ready for initial startup. Follow the rest of
the installation steps for the control you have (TIC or PLC).
3
* Overload modules on UL panel only.
Optional motor
starter protectors
with “UL” option