Technical information

When an alarm condition occurs, the Alarm light on the con-
trol panel lights and the control screen displays the alarm mes-
sage.
PLC C
ONTROL
A
NSWERING
ALARMS
Low Suction Pressure
Before an alarm can be reset with the acknowledge key, the
alarm condition must be cleared. Refer to the Alarm table and
the Troubleshooting tables to troubleshoot the alarm condi-
tion(s). After correcting the condition, remove the alarm from
the screen. Press and hold the Alarm Silence/Reset button for
a minimum of 3 seconds to remove alarm from screen. To
begin running the chiller again, press the Run button on the
Main screen.
STATUS SETUP RUN ALM
Press arrow
If there is a fault affecting compressor operation such as over-
load, high or low discharge pressure, compressor fault, etc.,
there is a three-minute delay before the compressor can be
started. The compressor light will flash quickly indicating that
manual reset is necessary. The manual reset should be per-
formed only after the alarm condition has been diagnosed and
corrected. The manual reset will start the compressor provided
all other permissive are enabled. To manually reset the com-
pressor, press the Alarm Silence button and the Enter button
simultaneously.
To view a list of the last 10 alarms, refer to Alarm History
Screens, in the Troubleshooting section of this manual. Alarms
are numbered and listed in order of occurrence, starting with
the most recent.
UGH024/1103 Portable Chillers
TROUBLESHOOTING
6-19