User guide

TrueBlend
Alarm Messages and
Troubleshooting
Edition: February 2008 115
Alarm Message
Possible Cause Solution
or
Too much material.
Display of screen only in
mode:
Component STOP:
Continue:
Batch is continued.
Alarm message is sent.
Stop:
Current component is
stopped, ERROR STOP
screen appears with "Incorrect
batch".
Alarm message is sent.
Component x not
enough material (in
the example, compo-
nent #3)
Component x too
much material
Component x not
proper weight (con-
nection from controller
to load cell is inter-
rupted, load cell defec-
tive, scales jammed or
overloaded, measured
values are faulty).
Controller malfunction
Make sure the material
hopper is full or has an
adequate material supply.
Make sure the material
dosing rate is correct. If
the rate is out of range
perform a material cali-
bration. See section
7.7.2.
Change the minimum/
maximum batch weight.
Limit the percentage
found on the model
screen.
Verify that the valves are
functioning correctly.