User guide
Function
4-24 l Operation
Control Function Descriptions(continued)
This screen shows the low CFM setpoint.
The default is 1 CFM. The default can be
changed with the proper password (see
page 4-29, screen 85).
This screen shows the alarm setpoint for a
Dewpoint alarm. With the proper pass-
word, it can be changed (see page 4-29,
screen 85). The defaults are -3°F for 180
seconds. If the control senses -3°F or
higher for 180 seconds, the dryer will
alarm.
This is the dewpoint high deviation alarm
value. With the proper password, it can be
changed (see page 4-29, screen 85). When
in dewpoint control, if the actual dewpoint
goes above the setpoint in screen 11, page
4-12, for the set amount of time, the dryer
will alarm “Dewpoint Deviation High”.
This is the dewpoint low deviation alarm
value. With the proper password, it can be
changed (see page 4-29, screen 85). When
in dewpoint control, if the actual dewpoint
goes below the setpoint in screen 11, page
4-12, by this value for this amount of time,
the dryer will alarm “Dewpoint Deviation
Low”.
Screen
SCREEN 66 (CFM Monitor
Option)
SCREEN 67 (Dewpoint Monitor
or Dewpoint Control)
SCREEN 68 (Dewpoint Control
Enabled)
SCREEN 71
SCREEN 69 (Dewpoint Control
Enabled)
DEWPOINT ALARM
ACT -40°F 180 SEC
DEWPOINT DEVIATION
HIGH 5°F 30 SEC
DEWPOINT DEVIATION
LOW 5°F 30 SEC
CFM LOW SETPOINT
1430