Technical information
26
230V FX Series Positioning Drive Reference Manual
Grounding
The GND terminals of the drive are internally bonded to the chassis. The enclosure and drive
grounds should be a common single point that ultimately is a continuous electrical path to
earth ground. Figure 17, "Suggested Grounding Example" illustrates the suggested grounding
arrangement.
Ground wires should not be shared with other equipment. Also ensure that metal to metal
contact is made between the ground lug and the cabinet back.
Figure 17: Suggested Grounding Example