Figure 15: Phase Delta/Delta Distribution to a Three-Phase WYE/WYE Isolation
Transformer
Figure 16: Three-Phase Delta/WYE Distribution to a Three-Phase WYE/WYE Isolation
Transformer
Transformer Sizing
Most applications will not require a transformer. However, in the following situations a
transformer may be required:
The secondary of the AC distribution transformer is not electrically referenced to earth
ground (i.e., left floating).
The nominal voltage available to the enclosure is greater than 240VAC. In this case, a
step-down transformer is needed.
The noise on the AC line is outside the suggested operating range of the equipment
connected to the AC line. In this case, an isolation transformer and/or line filter may be
required.
L3
L1
L2
EARTH
GROUND
3 PHASE ISOLATION TRANSFORMER
PRIMARY
DISTRIBUTION PANEL
L3
L1
L2
EARTH
GROUND
3 PHASE ISOLATION TRANSFORMER
DISTRIBUTION PANEL